Concrete Test Cylinder Calculator

How many strength test sets and cylinders a pour requires, and whether the results that came back satisfy the acceptance criteria.

ACI 318-08BNBC 2020
Save calculationFree account — your numbers come with you.

Code

The pour

The code counts each day's placing on its own; over several days the totals give the least it can need. Use Day by day for the exact count.

Specified strength

Not met — average of tests 2–4, 7–9 below f′c
No single test is below the floor, so no investigation: take steps to raise the average of later tests (ACI 318-08 §5.6.3.4). The concrete placed is not rejected.
Test sets required
5
Cylinders to cast
15
f′cmin12345678910
Minimum single test
3500 psi
Lowest test
3650 psi

Cylinder strengths

psi

One row per strength test: the cylinders from one sample, at least two 6 × 12 in (150 × 300 mm) or three 4 × 8 in (100 × 200 mm).

Test123Avg
14167
23883
34283
43750
54450
64117
73650
84250
94017
104417

Design checks

CheckDemandCapacityDCRStatus
Test 1 — individual strength3500 psi4167 psi0.840✓ OK
Test 2 — individual strength3500 psi3883 psi0.901✓ OK
Test 3 — individual strength3500 psi4283 psi0.817✓ OK
Tests 1–3 — running average4000 psi4111 psi0.973✓ OK
Test 4 — individual strength3500 psi3750 psi0.933✓ OK
Tests 2–4 — running average4000 psi3972 psi1.007✗ FAIL
Test 5 — individual strength3500 psi4450 psi0.787✓ OK
Tests 3–5 — running average4000 psi4161 psi0.961✓ OK
Test 6 — individual strength3500 psi4117 psi0.850✓ OK
Tests 4–6 — running average4000 psi4106 psi0.974✓ OK
Test 7 — individual strength3500 psi3650 psi0.959✓ OK
Tests 5–7 — running average4000 psi4072 psi0.982✓ OK
Test 8 — individual strength3500 psi4250 psi0.824✓ OK
Tests 6–8 — running average4000 psi4006 psi0.999✓ OK
Test 9 — individual strength3500 psi4017 psi0.871✓ OK
Tests 7–9 — running average4000 psi3972 psi1.007✗ FAIL
Test 10 — individual strength3500 psi4417 psi0.792✓ OK
Tests 8–10 — running average4000 psi4228 psi0.946✓ OK

Calculation

  1. 1Sets required by pour daysACI318 5.6.2
    n_{time} = \text{one set per day of placing}
    n_{time} = 3 \text{ days} \Rightarrow 3
    n_{time}3
  2. 2Sets required by volume placedACI318 5.6.2
    n_{vol} = \left\lceil \frac{V}{V_{set}} \right\rceil
    n_{vol} = \left\lceil \frac{400.0}{150} \right\rceil = 3
    n_{vol}3
  3. 3Sets required by surface areaACI318 5.6.2
    n_{area} = \left\lceil \frac{A}{A_{set}} \right\rceil
    n_{area} = \left\lceil \frac{12000}{5000} \right\rceil = 3
    n_{area}3

    A thin element can cover a large area on very little concrete, which the volume criterion alone would under-test.

  4. 4Governing number of test setsACI318 5.6.2
    n = \max\left(n_{time},\; n_{vol},\; n_{area}\right) \ge n_{min}
    n = \max(3,\,3,\,3) = 3,\quad n_{min} = 5 \Rightarrow 5
    n5

    The calculated criteria give 3; the ACI 318-08 minimum of 5 governs.

  5. 5Cylinders to cast
    N = n \times c
    N = 5 \times 3 = 15
    N15
  6. 6Lower bound on an individual strength testACI318 5.6.3.3(b)
    f_{min} = f'_c - 500\ \text{psi}
    f_{min} = 3500
    f_{min}3500 psi

Warnings

  • 2 acceptance checks are not met. Steps are required to raise the average of the strength tests that follow — a mix or procedure change, not rejection of the concrete already placed.

Notes

  • The code counts each day's placing on its own, so over 3 days these totals give the least the pour can need: a day with more than 150 yd³ needs more than one set that day. Enter each day's volume for the exact count.

Assumptions

  • One concrete class and one mix design. A pour with more than one class is tested for each class separately.
  • A cylinder entered as zero is treated as not cast, and is left out of that test's average.
  • Cylinder strengths are the values reported by the testing laboratory, already corrected for any specimen size or capping requirement.

What this calculator does not check

  • Counts the tests a pour requires and checks the results that came back. It does not evaluate the mix design, and it does not set a required average strength for proportioning.
  • Does not carry out the investigation that a failing result triggers — no core strength evaluation, load test or structural analysis.
  • Testing frequency is the code minimum. A specification or a superintending engineer can require more, and often does.
  • Assumes the tests are in chronological order, because the running average is taken over consecutive tests.

Results are for preliminary sizing and educational use. They are not a design and must be reviewed, verified and sealed by a licensed or registered engineer before being used in construction.